科技报告详细信息
Two-Phase Frictional Pressure Drop Multipliers for SUVA R-134a Flowing in a Rectangular Duct
Vassallo, P ; Keller, K
Knolls Atomic Power Laboratory
关键词: Refrigeration Suva R-134A;    Flow Rate;    Pressure Drop;    Ducts;    Suva R-134A;   
DOI  :  10.2172/850141
RP-ID  :  LM-04K165
RP-ID  :  DE-AC12-00SN39357
RP-ID  :  850141
美国|英语
来源: UNT Digital Library
PDF
【 摘 要 】

The adiabatic two-phase frictional multipliers for SUVA, R-134a flowing in a rectangular duct (with D{sub H} = 4.8 mm) have been measured for 3 nominal system pressures (0.9 MPa, 1.38 MPa and 2.41 MPa) and 3 nominal mass fluxes (510, 1020 and 2040 kg/m{sup 2}/s). The data is compared with several classical correlations to assess their predictive capabilities. The Lockhart-Martinelli model gives reasonable results at the lowest pressure and mass flux, near the operating range of most refrigeration systems, but gives increasingly poor comparisons as the pressure and mass flux is increased. The Chisholm B-coefficient model is found to best predict the data over the entire range of test conditions; however, there is significant disagreement at the highest pressure tested (with the model over predicting the data upwards of 100% for some cases). The data shows an increased tendency toward homogeneous flow as the pressure and flow rate are increased, and in fact the homogeneous model best predicts the bulk of the data at the highest pressure tested.

【 预 览 】
附件列表
Files Size Format View
850141.pdf 306KB PDF download
  文献评价指标  
  下载次数:34次 浏览次数:16次