IMPACTS OF REFRIGERANTLINE LENGTH ON SYSTEM EFFICIENCY IN RESIDENTIAL HEATING AND COOLING SYSTEMS USING REFRIGERANT DISTRIBUTION. | |
ANDREWS, J.W. | |
Brookhaven National Laboratory | |
关键词: Heat Transfer; Heating; Pressure Drop; 32 Energy Conservation, Consumption, And Utilization; Ducts; | |
DOI : 10.2172/785053 RP-ID : BNL--68550 RP-ID : AC02-98CH10886 RP-ID : 785053 |
|
美国|英语 | |
来源: UNT Digital Library | |
【 摘 要 】
The effects on system efficiency of excess refrigerant line length are calculated for an idealized residential heating and cooling system. By excess line length is meant refrigerant tubing in excess of the 25 R provided for in standard equipment efficiency test methods. The purpose of the calculation is to provide input for a proposed method for evaluating refrigerant distribution system efficiency. A refrigerant distribution system uses refrigerant (instead of ducts or pipes) to carry heat and/or cooling effect from the equipment to the spaces in the building in which it is used. Such systems would include so-called mini-splits as well as more conventional split systems that for one reason or another have the indoor and outdoor coils separated by more than 25 ft. This report performs first-order calculations of the effects on system efficiency, in both the heating and cooling modes, of pressure drops within the refrigerant lines and of heat transfer between the refrigerant lines and the space surrounding them.