科技报告详细信息
| Moisture Sensor for Sulfur Hexafluoride (SF6)-filled Circuit Breakers | |
| Sauers, I. | |
| Oak Ridge National Laboratory | |
| 关键词: Calibration; 24 Power Transmission And Distribution; Sulfur Fluorides; Moisture; Circuit Breakers; | |
| DOI : 10.2172/814463 RP-ID : C/ORNL96-0398 RP-ID : AC05-00OR22725 RP-ID : 814463 |
|
| 美国|英语 | |
| 来源: UNT Digital Library | |
PDF
|
|
【 摘 要 】
Measurements at ORNL were made on the Kahn moisture sensor which Doble Engineering wants to evaluate for use in SF{sub 6} circuit breakers. Test conducted at ORNL indicate that vacuum conditions, as might be found in SF{sub 6} circuit breakers prior to filling with SF{sub 6}, could lead to significant changes in calibration, resulting in erroneous readings of moisture content. Similar effects might also be observed in cases where SF{sub 6} byproducts are present, due the reactivity of some of these byproducts with water.
【 预 览 】
| Files | Size | Format | View |
|---|---|---|---|
| 814463.pdf | 740KB |
PDF