| LABORATORY EVALUATION OF THE DELTA Q TEST FOR DUCT LEAKAGE | |
| ANDREWS,J.W. | |
| Brookhaven National Laboratory | |
| 关键词: Blowers; Pressurization; 32 Energy Conservation, Consumption, And Utilization; Ducts; Residential Buildings; | |
| DOI : 10.2172/811286 RP-ID : BNL--71220-2003-IR RP-ID : AC02-98CH10886 RP-ID : 811286 |
|
| 美国|英语 | |
| 来源: UNT Digital Library | |
PDF
|
|
【 摘 要 】
Using a residential-size duct system in a controlled laboratory setting, the repeatability and accuracy of the Delta Q test for air leakage in residential duct systems have been measured. More than 100 Delta Q tests were performed. These were compared with results using fan pressurization and also with results of a procedure (Delta Q Plus) that uses leakage hole-size information to select the leakage pressures to be used in the Delta Q algorithm. The average error in supply or return leakage for the fan-pressurization test was 6.4% of system fan flow. For the Delta Q test it was 3.4% of fan flow, while for Delta Q Plus it was 1.9% of fan flow.