| Compressor Calorimeter Test of R-404A Alternatives ARM-31a, D2Y-65, L-40, and R32 + R-134a Mixture using a Scroll Compressor | |
| Shrestha, Som S1  Sharma, Vishaldeep1  Abdelaziz, Omar1  | |
| [1] ORNL | |
| 关键词: Alternative Refrigerants; Compressor; Calorimeter; Low GWP; | |
| DOI : 10.2172/1089777 RP-ID : ORNL/TM-2013/156 PID : OSTI ID: 1089777 Others : Other: BT0400000 Others : CEBT002 |
|
| 美国|英语 | |
| 来源: SciTech Connect | |
PDF
|
|
【 摘 要 】
As a contribution to the AHRI Low-GWP Alternative Refrigerants Evaluation Program (AREP), this study compares the performance of four lower-GWP alternative refrigerants, ARM-31a, D2Y-65, L-40, and R-32 + R-134a mixture, to that of refrigerant R-404A (baseline) in a scroll compressor designed for medium temperature refrigeration applications. These comparisons were carried out via compressor calorimeter tests performed on a compressor designed for refrigerant R-404A and having a nominal rated capacity of 23,500 Btu/hr. Tests were conducted over a suction dew point temperature range of -10 F to 35 F in 5 F increments and a discharge dew point temperature range of 70 F to 140 F in 10 F increments. All the tests were performed with 20 F superheat, 40 F superheat, and 65 F suction temperature. A liquid subcooling level of 10 F to 15 F was maintained for all the test conditions. However, the cooling capacities reported in this study are normalized for 0 F subcooling. The tests showed that the compressor energy efficiency ratio (EER) and cooling capacity with all four alternative refrigerants tested are higher at higher saturation suction and saturation discharge temperature and lower at lower saturation suction and saturation discharge temperature, compared to that of R-404A. Discharge temperatures of all the alternative refrigerants were higher than that of R-404A at all test conditions.
【 预 览 】
| Files | Size | Format | View |
|---|---|---|---|
| RO201704180002042LZ | 879KB |
PDF