科技报告详细信息
Compressor Calorimeter Test of R-404A Alternatives ARM-31a, D2Y-65, L-40, and R32 + R-134a Mixture using a Scroll Compressor
Shrestha, Som S1  Sharma, Vishaldeep1  Abdelaziz, Omar1 
[1] ORNL
关键词: Alternative Refrigerants;    Compressor;    Calorimeter;    Low GWP;   
DOI  :  10.2172/1089777
RP-ID  :  ORNL/TM-2013/156
PID  :  OSTI ID: 1089777
Others  :  Other: BT0400000
Others  :  CEBT002
美国|英语
来源: SciTech Connect
PDF
【 摘 要 】

As a contribution to the AHRI Low-GWP Alternative Refrigerants Evaluation Program (AREP), this study compares the performance of four lower-GWP alternative refrigerants, ARM-31a, D2Y-65, L-40, and R-32 + R-134a mixture, to that of refrigerant R-404A (baseline) in a scroll compressor designed for medium temperature refrigeration applications. These comparisons were carried out via compressor calorimeter tests performed on a compressor designed for refrigerant R-404A and having a nominal rated capacity of 23,500 Btu/hr. Tests were conducted over a suction dew point temperature range of -10 F to 35 F in 5 F increments and a discharge dew point temperature range of 70 F to 140 F in 10 F increments. All the tests were performed with 20 F superheat, 40 F superheat, and 65 F suction temperature. A liquid subcooling level of 10 F to 15 F was maintained for all the test conditions. However, the cooling capacities reported in this study are normalized for 0 F subcooling. The tests showed that the compressor energy efficiency ratio (EER) and cooling capacity with all four alternative refrigerants tested are higher at higher saturation suction and saturation discharge temperature and lower at lower saturation suction and saturation discharge temperature, compared to that of R-404A. Discharge temperatures of all the alternative refrigerants were higher than that of R-404A at all test conditions.

【 预 览 】
附件列表
Files Size Format View
RO201704180002042LZ 879KB PDF download
  文献评价指标  
  下载次数:13次 浏览次数:28次