科技报告详细信息
Compressor Calorimeter Test of R-410A Alternative: R-32/134a Mixture Using a Scroll Compressor
Shrestha, Som S1  Sharma, Vishaldeep1  Abdelaziz, Omar1 
[1] ORNL
关键词: Alternative Refrigerants;    Low GWP;    Compressor;    Calorimeter;    Heat Pump;   
DOI  :  10.2172/1131502
RP-ID  :  ORNL/TM-2013/414
PID  :  OSTI ID: 1131502
Others  :  Other: BT0101000
Others  :  BT0400000
Others  :  CEBT002
美国|英语
来源: SciTech Connect
PDF
【 摘 要 】

As a contribution to the AHRI Low-GWP Alternative Refrigerants Evaluation Program (AREP), this study compares the performance of lower-GWP alternative refrigerant R-32 + R-134a mixture, to that of refrigerant R-410A (baseline) in a scroll compressor designed for air-conditioning and heat pump applications. These comparisons were carried out via compressor calorimeter tests performed on a compressor designed for refrigerant R-410A and having a nominal rated capacity of 21,300 Btu/hr. Tests were conducted over a suction dew point temperature range of 10 F to 55 F in 5 F increments and a discharge dew point temperature range of 70 F to 140 F in 10 F increments. All the tests were performed with 20 F superheat, 40 F superheat, and 65 F suction temperature. A liquid subcooling level of 15 F was maintained for all the test conditions. The tests showed that the discharge temperature of the alternative refrigerant was higher than that of R-410A at all test conditions. Also, the energy efficiency ratio (EER) and cooling capacity of compressor using the alternative refrigerant were slightly lower in comparison to that of R-410A.

【 预 览 】
附件列表
Files Size Format View
543KB PDF download
  文献评价指标  
  下载次数:9次 浏览次数:31次