Compressor Calorimeter Test of R-410A Alternative: R-32/134a Mixture Using a Scroll Compressor | |
Shrestha, Som S1  Sharma, Vishaldeep1  Abdelaziz, Omar1  | |
[1] ORNL | |
关键词: Alternative Refrigerants; Low GWP; Compressor; Calorimeter; Heat Pump; | |
DOI : 10.2172/1131502 RP-ID : ORNL/TM-2013/414 PID : OSTI ID: 1131502 Others : Other: BT0101000 Others : BT0400000 Others : CEBT002 |
|
美国|英语 | |
来源: SciTech Connect | |
【 摘 要 】
As a contribution to the AHRI Low-GWP Alternative Refrigerants Evaluation Program (AREP), this study compares the performance of lower-GWP alternative refrigerant R-32 + R-134a mixture, to that of refrigerant R-410A (baseline) in a scroll compressor designed for air-conditioning and heat pump applications. These comparisons were carried out via compressor calorimeter tests performed on a compressor designed for refrigerant R-410A and having a nominal rated capacity of 21,300 Btu/hr. Tests were conducted over a suction dew point temperature range of 10 F to 55 F in 5 F increments and a discharge dew point temperature range of 70 F to 140 F in 10 F increments. All the tests were performed with 20 F superheat, 40 F superheat, and 65 F suction temperature. A liquid subcooling level of 15 F was maintained for all the test conditions. The tests showed that the discharge temperature of the alternative refrigerant was higher than that of R-410A at all test conditions. Also, the energy efficiency ratio (EER) and cooling capacity of compressor using the alternative refrigerant were slightly lower in comparison to that of R-410A.
【 预 览 】
Files | Size | Format | View |
---|---|---|---|
543KB | download |