Engineering Science and Technology, an International Journal | |
Improved finite control set model predictive control for distributed energy resource in islanded microgrid with fault-tolerance capability | |
Muhammad Aamir1  Muhammad Ali2  Muhammad Waqar Hassan2  Kimmo Kauhaniemi3  Hussain Sarwar Khan4  Mohsin Mumtaz4  | |
[1] Corresponding author.;Department of Electrical Engineering, Bahria University, Islamabad, Pakistan;Pak-Austria Fachhochschule, Institute of Applied Sciences and Technology, Haripur, Pakistan;School of Technology and Innovation, University of Vaasa, Finland; | |
关键词: Distributed energy resource; Fault-tolerance capability; MPC; Microgrid; | |
DOI : | |
来源: DOAJ |
【 摘 要 】
In this paper, improved finite control set model predictive voltage control (FCS-MPVC) is proposed for the distributed energy resource (DER) in AC islanded microgrid (MG). Typically, AC MGs have two or more power electronic-based DERs, which have the ability to maintain a constant voltage at the point of common coupling (PCC) as well as perform power sharing among the DERs. Though linear controllers can achieve above-mentioned tasks, they have several restrictions such as slow transient response, poor disturbance rejection capability etc. The proposed control approach uses mathematical model of power converter to anticipate the voltage response for possible switching states in every sampling period. The proposed dual-objective cost function is designed to regulate the output voltage as well as load current under fault condition. Two-step horizon prediction technique reduces the switching frequency and computational burden of the designed algorithm. Performance of the proposed control technique is demonstrated through MATLAB/Simulink simulations for single distributed generator (DG) and AC MG under linear and non-linear loading conditions. The investigated work presents an excellent steady state performance, low computational overhead, better transient performance and robustness against parametric variations in contrast to classical controllers. Total harmonic distortion (THD) for linear and non-linear load is 0.89% and 1.4% respectively as illustrated in simulation results. Additionally, the three-phase symmetrical fault current has been successfully limited to the acceptable range.
【 授权许可】
Unknown