The Journal of Engineering | |
Research on the influences of location selection and permeability of wind power generation on cascading failure | |
Wu Qi1  Yang Tian1  Li Longnv2  Liu Xiaoming2  | |
[1] School of Electrical Engineering, Shenyang University of Technology; | |
[2] Tianjin Key Laboratory of Advanced Electrical Engineering and Energy Technology, Tianjin Polytechnic University; | |
关键词: load flow; failure analysis; permeability; power grids; wind power plants; power generation faults; power generation reliability; electric betweenness; different location selection; wind power generation; power flow distribution; wind power penetration; permeability; severer cascading failure; localised abnormal flows; large-scale overload; site selection; nodes electric betweenness; IEEE30 system; | |
DOI : 10.1049/joe.2018.8702 | |
来源: DOAJ |
【 摘 要 】
The main cause for cascading failure is large-scale overload caused by localised abnormal flows. With the increase of wind power penetration, the complexity of flow distribution is strengthened. Therefore, it is necessary to study influences of site selection and permeability of wind power generation on cascading failure. An analysis method based on electric betweenness of nodes was put forward, and influences of permeability change on cascading failure on different location selection for wind power generation were researched. According to the study, it was found that when the electric betweenness was low, the overload of wind power led to declining uniformity of power flow distribution, resulting in transfer of flows to other lines. As a result, the heavy load of lines was further aggravated to promote the development of cascading failure. Simulation results of the IEEE30 system showed that with the increase of wind power penetration, the cascading failure was aggravated; and under the same permeability, the lower the electric betweenness of location selection was, the severer cascading failure would be.
【 授权许可】
Unknown