会议论文详细信息
3rd International Conference on Energy Engineering and Environmental Protection | |
System protection related technologies of power grid with high proportion of external ultra HVDC power | |
能源学;生态环境科学 | |
Lyu, Qi^1 ; Hou, Kaiyuan^2 ; Feng, Da^3 | |
Electric Engineering Department, Columbia University, New York | |
NY | |
10027, United States^1 | |
Northeast Branch, State Grid Corporation of China, Shenyang | |
110180, China^2 | |
Dept. of Electrical Engineering, Tsinghua University, Beijing | |
100084, China^3 | |
关键词: Double layer structure; Frequency characteristic; Generator-tripping; Multiplexing techniques; Optimal control strategy; Optimal strategies; Power supply construction; Real-time communication; | |
Others : https://iopscience.iop.org/article/10.1088/1755-1315/227/3/032024/pdf DOI : 10.1088/1755-1315/227/3/032024 |
|
学科分类:环境科学(综合) | |
来源: IOP | |
【 摘 要 】
High power DC blocking causes the high and low frequency problems respectively in the sending and receiving end grid. Considering the Ultra HVDC without direct corresponding power supply construction, the system protection with simple-reliable structure and real-time communication is set up against the frequency risk of sending end grid, and the global optimal strategy and precise control of generator tripping are realized. Covering the wind, hydro and thermal power of whole sending end grid, the system protection with double-layer structure is designed, multi-object oriented real-time communication multiplexing technique is studied, and the calculation method of frequency characteristic and precise generator tripping strategy is proposed. According to the characteristics of different types of power and its influence on the safe operation of power grid, the DC modulation and optimal control strategy of wind, hydro and thermal power are presented. The simulation results show that the system protection is effective and practical.【 预 览 】