会议论文详细信息
2018 International Conference on Advanced Technologies in Energy, Environmental and Electrical Engineering
Active Power Shifting Strategy for the Bipolar VSC-MTDC
能源学;生态环境科学;无线电电子学
Li, Zhou^1 ; He, Yan^1 ; Li, Yazhou^1 ; Gu, Wei^1 ; Xie, Jihua^1
School of Electrical Engineering, Southeast University, Nanjing
210096, China^1
关键词: Abnormal operation;    Generator-tripping;    Load-shedding;    Positive poles;    Practical projects;    Shifting strategy;    Transmission capacities;    Transmitted power;   
Others  :  https://iopscience.iop.org/article/10.1088/1755-1315/223/1/012042/pdf
DOI  :  10.1088/1755-1315/223/1/012042
学科分类:环境科学(综合)
来源: IOP
PDF
【 摘 要 】

Currently, the bipolar VSC-MTDC has become increasingly popular in practical projects. With the traditional wiring mode, line overload, generator tripping or load shedding may occur if a DC line or converter quits operation. While with a more flexible bipolar wiring mode, power shifting from the faulty network to the healthy one is permitted under same conditions. This paper proposes an active power shifting strategy based on bipolar VSC-MTDC. Since the positive-pole and negative-pole networks can be controlled independently, the transmitted power of the healthy pole network can be increased and that of the faulty pole network can be decreased, which is to avoid power surplus under abnormal operation conditions. This strategy has improved the reliability and transmission capacity of VSC-MTDC system. Then a 4-terminal MTDC simulation is established in PSCAD/EMTDC. The validity of the proposed strategy has been proved by the simulation results.

【 预 览 】
附件列表
Files Size Format View
Active Power Shifting Strategy for the Bipolar VSC-MTDC 1020KB PDF download
  文献评价指标  
  下载次数:10次 浏览次数:13次