会议论文详细信息
Indonesia Malaysia Research Consortium Seminar 2018
Symbiotic Organism Search for Sizing and Optimal Location of Distributed Generation Using Novel Sensitivity Factor
Setyawan, G.^1 ; Umar^1^2 ; Soeprijanto, A.^1 ; Penangsang, O.^1
Department of Electrical Engineering, Institut Teknologi Sepuluh Nopember, Indonesia^1
Department of Electrical Engineering, Universitas Khairun, Indonesia^2
关键词: Interconnected bus;    Location and sizings;    Optimal locations;    Performance indices;    Radial distribution networks;    Radial distribution systems;    Sensitivity factors;    Voltage profile improvement;   
Others  :  https://iopscience.iop.org/article/10.1088/1757-899X/588/1/012021/pdf
DOI  :  10.1088/1757-899X/588/1/012021
来源: IOP
PDF
【 摘 要 】

Electric power systems consist of many interconnected buses. The most widely used network topology is Radial Distribution Network (RDN), the bus located furthest from generation has a significant voltage drop and the number of buses without any support from Distributed Generation (DG) inflicting in increased power losses and increased generation cost. DG is advantageous to reduce power losses and increasing voltage on the power system, but the location and sizing of DG in the distribution network requires great consideration. In this paper the method used to determine the location is Loss Reduction Sensitivity Factor (LRSF) and Voltage Improvement Performance Index (VIPI) and for sizing DG uses artificial intelligence Symbiotic Organism Search (SOS). This DG locating and sizing problem is associated with real power loss minimization and voltage profile improvement objectives. The proposed method has been demonstrated on IEEE 33-bus radial distribution system. Based on this research the identification of using LRSF location is better than VIPI.

【 预 览 】
附件列表
Files Size Format View
Symbiotic Organism Search for Sizing and Optimal Location of Distributed Generation Using Novel Sensitivity Factor 1131KB PDF download
  文献评价指标  
  下载次数:4次 浏览次数:8次