Long Duration Performance of High Temperature Irradiation Resistant Thermocouples.
Rempe, J. ; Knudson, D. ; Condie, K. ; Cole, J.
Technical Information Center Oak Ridge Tennessee
关键词: Thermocouples;    In-pile instrumentation;    Material performance;    Molybdenum alloys;    Niobium alloys;   
RP-ID  :  DE2007912437
学科分类:工程和技术(综合)
美国|英语
来源: National Technical Reports Library
PDF
【 摘 要 】

Many advanced nuclear reactor designs require new fuel, cladding, and structural materials. Data are needed to characterize the performance of these new materials in high temperature, radiation conditions. However, traditional methods for measuring temperature inpile degrade at temperatures above 1100 oC. To address this instrumentation need, the Idaho National Laboratory (INL) developed and evaluated the performance of a high temperature irradiation-resistant thermocouple that contains alloys of molybdenum and niobium. To verify the performance of INLs recommended thermocouple design, a series of high temperature (from 1200 to 1800 oC) long duration (up to six months) tests has been initiated. This paper summarizes results from the tests that have been completed. Data are presented from 4000 hour tests conducted at 1200 and 1400 oC that demonstrate the stability of this thermocouple (less than 2% drift). In addition, post test metallographic examinations are discussed which confirm the compatibility of thermocouple materials throughout these long duration, high temperature tests.