Accuracy of CO2 sensors in commercial buildings: a pilotstudy
Fisk, William J. ; Faulkner, David ; Sullivan, Douglas P.
Lawrence Berkeley National Laboratory
关键词: Calibration;    Carbon Dioxide;    32;    Maintenance;    Commercial Buildings;   
DOI  :  10.2172/902450
RP-ID  :  LBNL--61862
RP-ID  :  DE-AC02-05CH11231
RP-ID  :  902450
美国|英语
来源: UNT Digital Library
PDF
【 摘 要 】

Carbon dioxide (CO{sub 2}) sensors are often deployed in commercial buildings to obtain CO{sub 2} data that are used to automatically modulate rates of outdoor air supply. The goal is to keep ventilation rates at or above code requirements, but to also to save energy by avoiding over ventilation relative to code requirements. However, there have been many anecdotal reports of poor CO{sub 2} sensor performance in actual commercial building applications. This study evaluated the accuracy of 44 CO{sub 2} sensors located in nine commercial buildings to determine if CO{sub 2} sensor performance, in practice, is generally acceptable or problematic. CO{sub 2} measurement errors varied widely and were sometimes hundreds of parts per million. Despite its small size, this study provides a strong indication that the accuracy of CO{sub 2} sensors used in commercial buildings is frequently less than is needed to measure peak indoor-outdoor CO{sub 2} concentration differences with less than a 20% error. Thus, we conclude that there is a need for more accurate CO{sub 2} sensors and/or better sensor maintenance or calibration procedures.