CFD analysis of LLNL downdraft table | |
Finlayson, Elizabeth U. ; Jayaraman, Buvana ; Kristoffersen, Astrid R. ; Gadgil, Ashok J. | |
Lawrence Berkeley National Laboratory | |
关键词: Blowers; Containment; Lawrence Livermore National Laboratory; Modifications; Geometry; | |
DOI : 10.2172/817257 RP-ID : LBNL--53883 RP-ID : AC03-76SF00098 RP-ID : 817257 |
|
美国|英语 | |
来源: UNT Digital Library | |
【 摘 要 】
This study examines the airflow and contaminant transport in an existing room (89 inch x 77 inch x 98 inch) that houses a downdraft table at LLNL. The facility was designed and built in the 1960's and is currently being considered for redesign. One objective of the redesign is to reduce airflow while maintaining or improving user safety. Because this facility has been used for many years to handle radioactive material it is impractical to conduct extensive experimental tests in it. Therefore, we have performed a Computational Fluid Dynamic (CFD) analysis of the facility. The study examines the current operational condition and some other cases with reduced airflow. Reducing airflow will lead to savings in operating costs (lower fan power consumption), and possible improvements in containment from reduced turbulence. In addition, we examine three design (geometry) changes. These are: (1) increasing the area of the HVAC inlet on the ceiling, (2) adding a 15{sup o} angled ceiling inlet and (3) increasing the area of the slot in the doorway. Of these three geometry modifications, only the larger doorway slot leads to improved predicted containment.
【 预 览 】
Files | Size | Format | View |
---|---|---|---|
817257.pdf | 402KB | download |