科技报告详细信息
Clean Firetube Boiler Waterside Heat Transfer Surfaces, Energy Tips: STEAM, Steam Tip Sheet #7 (Fact Sheet)
National Renewable Energy Laboratory (U.S.)
关键词: Heat Transfer;    Boilers;    Calcium;    Nrel;    Efficiency;   
DOI  :  10.2172/1039465
RP-ID  :  DOE/GO-102012-3597
RP-ID  :  AC36-08GO28308
RP-ID  :  1039465
美国|英语
来源: UNT Digital Library
PDF
【 摘 要 】
A steam energy tip sheet for the Advanced Manufacturing Office (AMO). The prevention of scale formation in firetube boilers can result in substantial energy savings. Scale deposits occur when calcium, magnesium, and silica, commonly found in most water supplies, react to form a continuous layer of material on the waterside of the boiler heat exchange tubes. Scale creates a problem because it typically possesses a thermal conductivity, an order of magnitude less than the corresponding value for bare steel. Even thin layers of scale serve as an effective insulator and retard heat transfer. The result is overheating of boiler tube metal, tube failures, and loss of energy efficiency. Fuel consumption may increase by up to 5% in firetube boilers because of scale. The boilers steam production may be reduced if the firing rate cannot be increased to compensate for the decrease in combustion efficiency. Energy losses as a function of scale thickness and composition are given. Any scale in a boiler is undesirable. The best way to deal with scale is not to let it form in the first place. Prevent scale formation by: (1) Pretreating of boiler makeup water (using water softeners, demineralizers, and reverse osmosis to remove scale-forming minerals); (2) Injecting chemicals into the boiler feedwater; and (3) Adopting proper boiler blowdown practices.
【 预 览 】
附件列表
Files Size Format View
1039465.pdf 408KB PDF download
  文献评价指标  
  下载次数:18次 浏览次数:73次