科技报告详细信息
Thermo-Fluids Provisioning of a High Performance High Density Data Center
Beitelmal, Monem H. ; Patel, Chandrakant D.
HP Development Company
关键词: data center;    high density;    server failure;    heat transfer;    modeling;    provisioning;    cooling;   
RP-ID  :  HPL-2004-146R1
学科分类:计算机科学(综合)
美国|英语
来源: HP Labs
PDF
【 摘 要 】

Consolidation and dense aggregation of slim compute, storage and networking hardware has resulted in high power density data centers. The high power density resulting from current and future generations of servers necessitates detailed thermo-fluids analysis to provision the cooling resources in a given data center for reliable operation. The analysis must also predict the impact on the thermo fluid distribution due to changes in hardware configuration and building infrastructure such as a sudden failure in data center cooling resources. The objective of the analysis is to assure availability of adequate cooling resources to match the heat load, which is typically non-uniformly distributed and characterized by high-localized power density. This study presents an analysis of an example modern data center with a view of the magnitude of temperature variation and impact of a failure. Initially, static provisioning for a given distribution of heat loads and cooling resources is achieved to produce a reference state. A perturbation in reference state is introduced to simulate a very plausible scenario -failure of a room air conditioning (CRAC) unit. The transient model shows the "redlining" of inlet temperature of systems in the area that is most influenced by the failed CRAC. In this example high-density data center, the time to reach unacceptable inlet temperature is less than 80 seconds based on an example temperature set point limit of 40°C (most of today's servers would require an inlet temperature below 35°C to operate). An effective approach to resolve this issue, if there is adequate capacity, is to migrate the compute workload to other available systems within the data center to reduce the inlet temperature to the servers to an acceptable level. 17 Pages

【 预 览 】
附件列表
Files Size Format View
RO201804100000940LZ 967KB PDF download
  文献评价指标  
  下载次数:19次 浏览次数:38次