| Plug and Process Loads Capacity and Power Requirements Analysis | |
| Sheppy, M. ; Gentile-Polese, L. | |
| 关键词: PLUG LOAD; PLUG AND PROCESS LOAD; PPL; COMMERCIAL BUILDING; Buildings; | |
| DOI : 10.2172/1158449 RP-ID : DOE/GO-102014-4277 PID : OSTI ID: 1158449 |
|
| 学科分类:能源(综合) | |
| 美国|英语 | |
| 来源: SciTech Connect | |
PDF
|
|
【 摘 要 】
This report addresses gaps in actionable knowledge that would help reduce the plug load capacities designed into buildings. Prospective building occupants and real estate brokers lack accurate references for plug and process load (PPL) capacity requirements, so they often request 5-10 W/ft2 in their lease agreements. Limited initial data, however, suggest that actual PPL densities in leased buildings are substantially lower. Overestimating PPL capacity leads designers to oversize electrical infrastructure and cooling systems. Better guidance will enable improved sizing and design of these systems, decrease upfront capital costs, and allow systems to operate more energy efficiently. The main focus of this report is to provide industry with reliable, objective third-party guidance to address the information gap in typical PPL densities for commercial building tenants. This could drive changes in negotiations about PPL energy demands.
【 预 览 】
| Files | Size | Format | View |
|---|---|---|---|
| 619KB |
PDF