Multilevel cascaded three-phase inverter with low-voltage ride-through flexible control capability for photovoltaic systems; pp. 331–345
article
Omar Kanaan Kanaan Albasri1  Ergun Erçelebi1 
[1] Faculty of Electrical and Computer Engineering, Gaziantep University 27310 Sahinbey
关键词: power electronics;    photovoltaic systems;    multilevel cascaded H-bridge inverter;    asymmetric voltage sag;    low-voltage Key words: power electronics;    photovoltaic systems;    multilevel cascaded H-bridge inverter;    asymmetric voltage sag;    low-voltage ride-through;   
DOI  :  10.3176/proc.2020.4.08
学科分类:内科医学
来源: Teaduste Akadeemia Kirjastus
PDF
【 摘 要 】

A potential solution for medium and large-scale solar power plants connected to a grid is the multilevel cascade H- bridge (CHB) inverter. Nevertheless, it has not been thoroughly studied how it operates during voltage sags. An easy strategy for controlling the operation of solar grid-connected CHB inverters in periods of unstable voltage sags is presented in this paper. The main contribution of this study is the fact that the proposed strategy is capable of infusing both reactive power, which represents the so-called low-voltage ride-through capability (LVRT), and active power into the grid with either stable or unstable currents, the so-called low-voltage ride-through capability (LVRT), and active power into the grid with either stable or unstable currents, as well as maintaining voltage balance of all DC-link capacitors. To obtain gate signals, phase-shifted sinusoidal pulse width modulation (PWM) technique is applied. Under various unbalanced voltage sags, the performance of the proposed strategy for the operation of a grid-connected CHB converter was illustrated and validated through a computer simulation platform. Moreover, an experimental setup for a 5-level CHB inverter using MOSFET switches with 5 kHz switching frequency was implemented to reveal the effectiveness of the proposed strategy. The Texas instrument DSP C2000 micro-controller TMS320F28335 was used to detect control, modulation and protection functions in real time and simultaneously. The developed system was tested under severe and light unbalance conditions, and the results show that this system can handle a single-phase voltage sag and be used as a practical light unbalance conditions, and the results show that this system can handle a single-phase voltage sag and be used as a practical device for AC grids.

【 授权许可】

CC BY   

【 预 览 】
附件列表
Files Size Format View
RO202307160003620ZK.pdf 3651KB PDF download
  文献评价指标  
  下载次数:10次 浏览次数:7次