期刊论文详细信息
International Journal of Advanced Research in Electrical, Electronics and Instrumentation Engineering
Flexible Voltage Control Scheme forDistributed Generation Systems under GridFault
article
T.Nelson1  D.Mary2 
[1] Government College of Technology;Department of EIE, Government College of Technology
关键词: Distributed generation (DG);    grid-connected inverter;    reactive power control;    voltage sag;    grid fault.;   
来源: Research & Reviews
PDF
【 摘 要 】

During voltage sags, continuous power delivery from distributed generation systems to the grid is desirable for the purpose of grid support. Ancillary services for distributed generation (DG) systems become a challenging issue to integrate renewable-energy sources into the grid. Voltage control is one of these ancillary services which can ride through and support the voltage under grid faults. In order to facilitate the control of distributed generation systems adapted to the expected change of grid requirements, flexible voltage support control scheme is proposed for inverter based distributed generation, aiming at regulating voltage limits and reactive power injection to remain connected and supports the grid under fault. In three-phase balanced voltage sags, the inverter should inject reactive power in order to raise the voltage in all phases. In one- or two-phase faults, the main concern of the DG inverter is to equalize voltages by reducing the negative symmetric sequence and clear the phase jump. Thus, over and under voltage can be avoided, and the proposed control scheme prevents disconnection while achieving the desired voltage support service which can be analyzed and simulated by using Matlab/Simulink environment. The main contribution of this work is the introduction of a control algorithm for reference current generation that provides flexible voltage support under grid faults.

【 授权许可】

Unknown   

【 预 览 】
附件列表
Files Size Format View
RO202307140001426ZK.pdf 476KB PDF download
  文献评价指标  
  下载次数:5次 浏览次数:0次