期刊论文详细信息
Energy Reports
Power system equivalent inertia evaluation algorithm based on intelligent optimization
Peng Ye1  Xiaoyi Qian2  Yi Zhao2  Qiang Zhang3  Xinwei Li3  Chao Wang3 
[1] Corresponding author.;Shenyang Institute of Engineering, 18 Puchang Road, Shenbei New District, Shenyang 110036, China;State Grid Liaoning Electric Power Co., LTD. Electric Power Research Institute, 39-7 Siping Street, Heping District, Shenyang 110006, China;
关键词: Power system;    Equivalent inertia;    Inertial time constant;    Frequency change rate;   
DOI  :  
来源: DOAJ
【 摘 要 】

To improve the accuracy of the evaluation of the equivalent inertia of a power system, a method for evaluating the equivalent inertia level of a power system based on an intelligent optimization algorithm is proposed. The proposed method constructs the objective function based on different degrees of system perturbation, ignores the frequency characteristics of the load, constructs the objective function with the generator swing equation, solves the inertia time constant of each generator using the intelligent optimization algorithm, and then evaluates the equivalent inertia of the whole system, eliminates the influence of inconsistent frequency change rate under perturbation on the system equivalent inertia evaluation, and thus obtains a more accurate system equivalent inertia evaluation, experimental result shows the evaluation accuracy can be improved by 10.79% and 3.48% respectively compared with other two comparison method.

【 授权许可】

Unknown   

  文献评价指标  