IEEE Access
Partial Discharge Localization Using Electromagnetic Time Reversal: A Performance Analysis
Gevork B. Gharehpetian1  Ali Ghasemi2  Farhad Rachidi3  Zhaoyang Wang3  Hamidreza Karami3  Hossein Karami4  Marcos Rubinstein5  Mohammad Azadifar5 
[1] Department of Electrical Engineering, Amirkabir University of Technology (Tehran Polytechnic), Tehran, Iran;Department of Electrical Engineering, Shahed University, Tehran, Iran;Electromagnetic Compatibility Laboratory, Swiss Federal Institute of Technology (EPFL), Lausanne, Switzerland;High-Voltage Research Group, Niroo Research Institute, Tehran, Iran;Institute for Information and Communication Technologies (IICT), University of Applied Sciences of Western Switzerland (HES-SO), Yverdon-les-Bains, Switzerland;
关键词: Experimental analysis;    partial discharge localization;    time difference of arrival;    electromagnetic time reversal process;    transformer tank;   
DOI  :  10.1109/ACCESS.2020.3015973
来源: DOAJ
【 摘 要 】

In this study, first, a comparison on the application of electromagnetic time reversal (EMTR) and time difference of arrival (TDoA) in partial discharge localization in power transformers is presented. A two-dimensional finite-difference time-domain simulation is used to calculate the signal recorded by the sensors. Results show that, in a transformer tank excluding its windings, both methods yield similar results in terms of location accuracy, although the EMTR method only needs one sensor to localize the partial discharge (PD) source while the TDoA method needs at least three sensors in the 2D localization problem. However, the presence of transformer windings leads to a degradation of the performance of the TDoA method if the line of sight from the source to the sensor is blocked by any of the winding blocks. On the other hand, the presence of the transformer windings has an effect on the localization of PD sources that occur between two adjacent phase windings when the distance between the outer winding distances is shorter than the minimum wavelength, λmin. The degradation is directly caused by the diffraction limit. It is shown that, if the distance between two adjacent phase windings is greater than λmin, the EMTR process can locate PD sources occurring between two adjacent phase windings with acceptable accuracy. A case of occurrence of PDs in close proximity (less than λmin/2) to a single metallic object is analyzed both numerically and experimentally. The analysis reveals that although a degradation in the accuracy of the localization is observed compared to the case of longer distances between the PD source and the metallic object, a reasonable localization error of 10 mm (corresponding to λmin/10) is obtained.

【 授权许可】

Unknown   

  文献评价指标  
  下载次数:0次 浏览次数:0次