期刊论文详细信息
Protection and Control of Modern Power Systems
High performance decoupled active and reactive power control for three-phase grid-tied inverters using model predictive control
Mohamed Azab1 
[1]EEET Department, Yanbu Industrial College, Yanbu AL Sinaiyah, Saudi Arabia
[2]EEET Department, Faculty of Engineering, Benha University, Banha, Egypt
关键词: Model predictive control;    Finite control set;    Grid-connected inverter;    Active power;    Reactive power;    Distributed generation;    Low voltage ride through;    PQ theory;    FCS-MPC;    LVRT;   
DOI  :  10.1186/s41601-021-00204-z
来源: Springer
PDF
【 摘 要 】
Finite control set-model predictive control (FCS-MPC) is employed in this paper to control the operation of a three-phase grid-connected string inverter based on a direct PQ control scheme. The main objective is to achieve high-performance decoupled control of the active and reactive powers injected to the grid from distributed energy resources (DER).The FCS-MPC scheme instantaneously searches for and applies the optimum inverter switching state that can achieve certain goals, such as minimum deviation between reference and actual power; so that both power components (P and Q) are well controlled to their reference values.In addition, an effective method to attenuate undesired cross coupling between the P and Q control loops, which occurs only during transient operation, is investigated. The proposed method is based on the variation of the weight factors of the terms of the FCS-MPC cost function, so a higher weight factor is assigned to the cost function term that is exposed to greater disturbance. Empirical formulae of optimum weight factors as functions of the reference active and reactive power signals are proposed and mathematically derived. The investigated FCS-MPC control scheme is incorporated with the LVRT function to support the grid voltage in fulfilling and accomplishing the up-to-date grid codes. The LVRT algorithm is based on a modification of the references of active and reactive powers as functions of the instantaneous grid voltage such that suitable values of P and Q are injected to the grid during voltage sag.The performance of the elaborated FCS-MPC PQ scheme is studied under various operating scenarios, including steady-state and transient conditions. Results demonstrate the validity and effectiveness of the proposed scheme with regard to the achievement of high-performance operation and quick response of grid-tied inverters during normal and fault modes.
【 授权许可】

CC BY   

【 预 览 】
附件列表
Files Size Format View
RO202108125784291ZK.pdf 3398KB PDF download