期刊论文详细信息
Journal of control, automation and electrical systems
Robust Control of Three-Phase VSI with LCL Filter for Distributed Generation Power Quality Improvement
article
Peña, José Carlos Ugaz1  Sampaio, Leonardo Poltronieri2  de Brito, Moacyr Aureliano Gomes3  Canesin, Carlos Alberto1 
[1] Power Electronics Laboratory, São Paulo State University-UNESP;Federal University of Technology-Paraná-UTFPR;Department of Electrical Engineering – DEL, Federal University of Mato Grosso do Sul-UFMS
关键词: Grid-connected inverter;    LCL filter;    Linear matrix inequalities (LMIs);    Microgrid inverter;    Robust control;   
DOI  :  10.1007/s40313-020-00610-y
学科分类:自动化工程
来源: Springer
PDF
【 摘 要 】

This paper proposes a methodology to control a three-phase voltage source inverter with LCL filter for distributed generation (DG) in microgrid scenario. Thus, the presented control strategy allows the DG system to operate in both grid-connected and islanded modes with a smooth transition between them. Therefore, the DG control system strategy is performed by splitting the control input into two control-stages; the first one is in charge of reproducing sinusoidal voltages at the filter capacitors; meanwhile, the second is dedicated to modulate these voltages in order to achieve proper amplitude and phase for correct output current injection. By means of discrete-time state-space representation of the system, state-feedback controllers are obtained employing linear matrix inequalities considering uncertainties on grid inductances and optimization of the H2 norm for each operation mode. Finally, the feasibility of the proposed DG system is demonstrated and validated through computational simulations, as well as experimental evaluations.

【 授权许可】

CC BY   

【 预 览 】
附件列表
Files Size Format View
RO202108090001192ZK.pdf 3572KB PDF download
  文献评价指标  
  下载次数:14次 浏览次数:5次