期刊论文详细信息
Energies
On the Feasibility of Using Poles Computed from Frequency Domain Spectroscopy to Assess Oil Impregnated Paper Insulation Conditions
Yazid Hadjadj2  Fethi Meghnefi2  Issouf Fofana1 
[1] Canada Research Chair on Insulating Liquids and Mixed Dielectrics for Electrotechnology (ISOLIME), Université du Québec à Chicoutimi, 555 Boulevard de l’université, Chicoutimi, QC G7H 2B1, Canada;
关键词: dielectric spectroscopy;    dielectric dissipation factor;    moisture content;    oil-paper insulation;    poles;   
DOI  :  10.3390/en6042204
来源: mdpi
PDF
【 摘 要 】

Frequency Domain Spectroscopy (FDS) is an effective tool allowing assessing the condition of oil-paper insulation system in power equipment. However, results from these measurements are known to be greatly influenced by various parameters, including insulation aging, moisture content, and insulation geometry/volume, together with environmental condition such as temperature. In this contribution, a series of experiments have been performed under controlled laboratory conditions. The dielectric response of the oil impregnated paper, along with the degree of polymerization and moisture content, were monitored. Since dielectric parameters are geometry dependent, poles (independent of the geometry) which depends on resistivity and permittivity, were considered to assess the condition of the insulation. From the investigations performed on new and aged samples, it is shown that poles (P) can be regarded as insulation aging indicator. It is also shown that a per unit value based on the Dielectric Dissipation Factor (DDF), measured in the frequency range from 1 to 1000 Hz can be correlated to moisture content in the insulation paper.

【 授权许可】

CC BY   
© 2013 by the authors; licensee MDPI, Basel, Switzerland.

【 预 览 】
附件列表
Files Size Format View
RO202003190036934ZK.pdf 356KB PDF download
  文献评价指标  
  下载次数:7次 浏览次数:7次