Entropy
Exergy Analysis of a Ground-Coupled Heat Pump Heating System with Different Terminals
Xiao Chen2  Xiaoli Hao1 
[1] College of Energy and Safety Engineering, Hunan University of Science and Technology, Xiangtan, 411201, China; E-Mail:;Department of Architectural Engineering, Hunan Institute of Engineering, Xiangtan, 411104, China
关键词: ground-coupled heat pump;    exergy analysis;    exergy loss;    exergy efficiency;    radiant floor;    fan coil unit;   
DOI  :  10.3390/e17042328
来源: mdpi
PDF
【 摘 要 】

In order to evaluate and improve the performance of a ground-coupled heat pump (GCHP) heating system with radiant floors as terminals, an exergy analysis based on test results is performed in this study. The system is divided into four subsystems, and the exergy loss and exergy efficiency of each subsystem are calculated using the expressions derived based on exergy balance equations. The average values of the measured parameters are used for the exergy analysis. The analysis results show that the two largest exergy losses occur in the heat pump and terminals, with losses of 55.3% and 22.06%, respectively, and the lowest exergy efficiency occurs in the ground heat exchange system. Therefore, GCHP system designers should pay close attention to the selection of heat pumps and terminals, especially in the design of ground heat exchange systems. Compared with the scenario system in which fan coil units (FCUs) are substituted for the radiant floors, the adoption of radiant floors can result in a decrease of 12% in heating load, an increase of 3.24% in exergy efficiency of terminals and an increase of 1.18% in total exergy efficiency of the system. The results may point out the direction and ways of optimizing GCHP systems.

【 授权许可】

CC BY   
© 2015 by the authors; licensee MDPI, Basel, Switzerland

【 预 览 】
附件列表
Files Size Format View
RO202003190013754ZK.pdf 765KB PDF download
  文献评价指标  
  下载次数:5次 浏览次数:55次