Proceedings | |
A Sub-Zonal PMV-Based HVAC and Façade Control System for Curtain Wall Buildings | |
Pietroni, Filippo1  Arnesano, Marco2  Calvaresi, Andrea3  Zampetti, Lorenzo4  | |
[1] Author to whom correspondence should be addressed.;Department of Industrial Engineering and Mathematical Sciences, Università Politecnica delle Marche, via Brecce Bianche 12, 60131 Ancona, Italy;Focchi Spa, via Cornacchiara, 47824 Poggio Torriana (RN), Italy;Presented at the Sustainable Places (SP 2018), Aix-les Bains, France, 27â29 June 2018 | |
关键词: monitoring; façade; HVAC; comfort; energy; optimization; | |
DOI : 10.3390/proceedings2151138 | |
学科分类:社会科学、人文和艺术(综合) | |
来源: mdpi | |
【 摘 要 】
This paper presents an experimental test room in a curtain wall building where an innovative monitoring and control system was implemented and tested. The proposed solution is composed by an IR-based comfort sensor that measures the PMV (Predicted Mean Vote) index for 2 roomâs sub-zones and provides the optimal air temperature set-points. The overall control system includes a distributed sensors and actuators network, also embedded into the façade modules, to measure indoor and outdoor parameters and to regulate fan-coils, windows opening and shadings with a sub-zonal approach. Initial results turn out to provide an energy saving of about 20% with an improvement of thermal/visual comfort and IAQ conditions.
【 授权许可】
CC BY
【 预 览 】
Files | Size | Format | View |
---|---|---|---|
RO201910252806982ZK.pdf | 173KB | download |