Reducing uncertainty – responses for electricity utilities to severe solar storms
Charles Trevor Gaunt1 
[1] University of Cape Town,Rondebosch,Cape Town,South Africa
关键词: condition monitoring;    transformers;    reliability;    power systems;    geomagnetically induced currents;   
Others  :  800612
DOI  :  doi:10.1051/swsc/2013058
 received in 2013-05-03, accepted in 2013-12-23,  发布年份 2014
PDF
【 摘 要 】

Until recently, electricity utilities in mid- and low-latitude regions believed that solar storms had no (or only insignificant) effect on their power systems. Then it was noticed that the onset of damage in several large transformers, leading to their failure, correlated very closely with the Halloween storm of 2003. Since then engineers have started to appreciate that a very severe storm could have serious consequences outside the high-latitude regions. There are many uncertainties in predicting the effects of solar storms on electrical systems. The severity and time of arrival of a storm are difficult to model; so are the geomagnetically induced currents (GICs) expected to flow in the power networks. Published information about the responses of different types of transformers to GICs is contradictory. Measurements of the abnormal power flows in networks during solar storms generally do not take into account the effects of the current distortion and unbalance, potentially giving misleading signals to the operators. The normal requirement for optimum system management, while allowing for the possibility of faults caused by lightning, birds and other causes, limits the capacity of system operators to respond to the threats of GICs, which are not assessed easily by the N − 1 reliability criterion. A utility’s response to the threat of damage by GICs depends on the expected frequency and magnitude of solar storms. Approaches to formulating a response are located in a system model incorporating space physics, network analysis, transformer engineering, network reliability and decision support and the benefits are identified. Approaches adopted in high-latitude regions might not be appropriate where fewer storms are expected to reach damaging levels. The risks of an extreme storm cannot be ignored, and understanding the response mechanisms suitable for low-latitude regions has the capacity to inform and reduce the uncertainty for power systems planners and operators worldwide.

【 授权许可】

   
© C.T Gaunt, Published by EDP Sciences 2014

【 预 览 】
附件列表
Files Size Format View
20140707194427922.pdf 795KB PDF download
Fig. 5. 57KB Image download
Fig. 4. 49KB Image download
Fig. 3. 22KB Image download
Fig. 2. 59KB Image download
Fig. 1. 21KB Image download
【 图 表 】

Fig. 1.

Fig. 2.

Fig. 3.

Fig. 4.

Fig. 5.

【 参考文献 】
  • [1]Andersson, G., P. Donalek, R. Farmer, N. Hatziargyriou, and I. Kamwa, Causes of the 2003 major grid blackouts in North America and Europe, and recommended means to improve system dynamic performance, IEEE Transactions on Power Systems, 20 (4), 1922–1928, 2005.
  • [2]Bernhardi, E.H., T.A. Tjimbandi, P.J. Cilliers, and C.T. Gaunt, Improved calculation of geomagnetically induced currents in power networks in low-latitude regions, Power Systems Computation Conference, Glasgow, pp. 1391–1395, IBSN 978-1-61738-857-6, 2008.
  • [3]Dzobo, O, C.T. Gaunt, and R. Herman, Investigating the use of probability distribution functions in reliability-worth analysis of electric power systems, Int. J. Electr. Power Energy Syst., 37 (1), 110–116, DOI: 10.1016/j.ijepes.2011.12.013, 2012.
  • [4]Edimu, M., K. Alvehag, C.T. Gaunt, and R. Herman, Analyzing the performance of a time-dependent probabilistic approach for bulk network reliability assessment, Electr. Power Syst. Res., 104, 156–163, DOI: 10.1016/j.epsr.2013.06.016, 2013.
  • [5]Gaunt, C.T., and G. Coetzee, Transformer failures in regions incorrectly considered to have low GIC-risk. IEEE PowerTech, Lausanne, 807–812, DOI: 10.1109/PCT.2007.4538419, 2007.
  • [6]Gaunt, C.T., and M. Malengret, Why we use the term non-active power, and how it can be measured under non-ideal power supply conditions, Power Engineering Society Conf. and Expo. in Africa (PowerAfrica), Johannesburg, 9–13 July 2012, DOI: 10.1109/PowerAfrica.2012.6498641, 2012.
  • [7]Kappenman, J.G., and V.D. Albertson, Bracing for the Geomagnetic Storms, IEEE Spectrum Magazine, (March), 27–33, 1990.
  • [8]Liu, C.M., L.G. Liu, and R. Pirjola, Geomagnetically induced currents in the high-voltage power grid in China, IEEE Trans. Power Delivery, 24, 4, 2009.
  • [9]Malengret, M., and C.T. Gaunt, General theory of average power for multi-phase systems with distortion, unbalance and direct current components, Electr. Power Syst. Res., 84, 224–230, DOI: 10.1016/j.epsr.2011.11.020, 2011.
  • [10]Ministry of Power, Report of the Enquiry Committee on Grid Disturbance in Northern Region on 30th July 2012 and in Northern, Eastern & North-Eastern Region on 31st July 2012, New Delhi, 2012.
  • [11]Minnaar, U.J., C.T. Gaunt, and F. Nicolls, Characterisation of power system events on South African transmission power lines, Electr. Power Syst. Res., 88, 25–32, DOI: 10.1016/j.epsr.2012.01.015, 2012.
  • [12]Molinski, T.S., Why utilities respect geomagnetically induced currents, J. Atmos. Sol. Terr. Phys., 64 (16), 1765–1778, 2002.
  • [13]Moodley, N., and C.T. Gaunt, Developing a power transformer low energy degradation assessment triangle, Power Engineering Society Conf. and Expo. in Africa (PowerAfrica), Johannesburg, 9–13 July, DOI: 10.1109/PowerAfrica.2012.6498647, 2012.
  • [14]NERC, Special reliability assessment interim report: Effects of geomagnetic disturbances on the bulk power system. North American Electric Reliability Corporation, Atlanta, GA, 2012.
  • [15]Oyedokun, D.T., M. Simon, and C.T. Gaunt, Introduction of a more detailed calculation of geomagnetically induced currents in transmission networks, Proc. of Southern African Universities’ Power Engineering Conference, Potchefstroom, pp. 211–215, 2013.
  • [16]Oyedokun, D.T., C.T. Gaunt, S. Tenbohlen, M. Heindl, M. Beltle, M. Reuter, and D. Schneider, Laboratory test for GIC effects on power transformers, XVII International Symposium on High Voltage Engineering, VDE-Verlag, Berlin, Offenbach, 2011.
  • [17]Pulkkinen, A., E. Bernabeu, J. Eichner, C. Beggan, and A.W.P. Thomson, Generation of 100-year geomagnetically induced current scenarios, Space Weather, 10, S04003, DOI: 10.1029/2011SW000750, 2012.
  • [18]Thomson, A.W.P., E.B. Dawson, and S.J. Reay, Quantifying extreme behavior in geomagnetic activity, Space Weather, 9, S10001, DOI: 10.1029/2011SW000696, 2011.
  • [19]Thomson, A.W.P., C.T. Gaunt, P. Cilliers, J.A. Wild, B. Opperman, L.-A. McKinnell, P. Kotze, C.M. Ngwira, and S.I. Lotz, Present day challenges in understanding the geomagnetic hazard to national power grids, Adv. Space Res., 45 (9), 1182–1190, 2010.
  • [20]Torta, J.M., L. Serrano, J.R. Regué, A.M. Sánchez, and E. Roldán, Geomagnetically induced currents in a power grid of Northeastern Spain, Space Weather, 10, S06002, DOI: 10.1029/2012SW000793, 2012.
  文献评价指标  
  下载次数:83次 浏览次数:38次