A Method for Harmonic Sources Detection based on Harmonic Distortion Power Rate
材料科学;能源学
Lin, Ruixing^1 ; Xu, Lin^1 ; Zheng, Xian^2
State Grid Sichuan Electrical Power Research Institute, Chengdu, China^1
College of Electrical Engineering and Information Technology, Sichuan University, Chengdu, China^2
关键词: Background harmonics;    Distortion power;    Harmonic mitigation;    Harmonic source location;    Harmonic sources;    MATLAB /simulink;    Point of common coupling;    Prior information;   
Others  :  https://iopscience.iop.org/article/10.1088/1757-899X/322/7/072038/pdf
DOI  :  10.1088/1757-899X/322/7/072038
学科分类:材料科学(综合)
来源: IOP
PDF
【 摘 要 】

Harmonic sources detection at the point of common coupling is an essential step for harmonic contribution determination and harmonic mitigation. The harmonic distortion power rate index is proposed for harmonic source location based on IEEE Std 1459-2010 in the paper. The method only based on harmonic distortion power is not suitable when the background harmonic is large. To solve this problem, a threshold is determined by the prior information, when the harmonic distortion power is larger than the threshold, the customer side is considered as the main harmonic source, otherwise, the utility side is. A simple model of public power system was built in MATLAB/Simulink and field test results of typical harmonic loads verified the effectiveness of proposed method.