Thermal environmental case study of an existing underfloor air distribution (UFAD) system in a high-rise building in the tropics | |
材料科学;物理学 | |
Ya, Y.H.^1 ; Poh, K.S.^1 | |
Department of Mechanical Engineering, University of Malaya, Kuala Lumpur | |
50603, Malaysia^1 | |
关键词: Electrical equipment; Energy-efficiency strategies; Indoor air pollutants; Indoor environmental quality; Sick building syndrome; Supply air temperature; Underfloor air distribution systems; Underfloor air distributions; | |
Others : https://iopscience.iop.org/article/10.1088/1757-899X/88/1/012064/pdf DOI : 10.1088/1757-899X/88/1/012064 |
|
学科分类:材料科学(综合) | |
来源: IOP | |
【 摘 要 】
The performance of an existing underfloor air distribution (UFAD) system in a renowned high-rise office tower in Malaysia was studied to identify the root cause issues behind the poor indoor air quality. Occupants are the best thermal sensor. The building was detected with the sick building syndrome (SBS) that causes runny noses, flu-like symptoms, irritated skin, and etc. Long period of exposure to indoor air pollutants may increase the occupant's health risk. The parameters such as the space temperature, relative humidity, air movement, air change, fresh air flow rate, chilled water supply and return are evaluated at three stories that consist of five open offices. A full traverse study was carried out at one of the fresh air duct. A simplified duct flow measurement method using pitot-tubes was developed. The results showed that the diffusers were not effective in creating the swirl effect to the space. Internal heat gain from human and office electrical equipment were not drawn out effectively. Besides, relative humidity has exceeded the recommended level. These issues were caused by the poor maintenance of the building. The energy efficiency strategy of the UFAD system comes from the higher supply air temperature. It may leads to insufficient cooling load for the latent heat gained under improper system performance. Special care and considerations in design, construction and maintenance are needed to ensure the indoor air quality to be maintained. Several improvements were recommended to tackle the existing indoor air quality issues. Solar system was studied as one of the innovative method for retrofitting.
【 预 览 】
Files | Size | Format | View |
---|---|---|---|
Thermal environmental case study of an existing underfloor air distribution (UFAD) system in a high-rise building in the tropics | 961KB | download |