14th High-Tech Plasma Processes Conference | |
Experimental investigations on arc movement and commutation in the Low-Voltage Circuit Breaker | |
Quéméneur, Jean^1 ; Masquère, Mathieu^1 ; Freton, Pierre^1 ; Gonzalez, Jean-Jacques^1 ; Joyeux, Patrice^2 | |
Université de Toulouse, UPS, CNRS, INPT, LAPLACE (Laboratoire Plasma et Conversion d'Energie), 118 route de Narbonne, Toulouse Cedex 9 | |
F-31062, France^1 | |
Hager Electro SAS, 132 boulevard d'Europe, Obernai | |
67210, France^2 | |
关键词: Current sources; Experimental investigations; Experimental set up; High intensity arcs; High speed imaging; Low voltage circuit breakers; Moving contact; Post-treatment method; | |
Others : https://iopscience.iop.org/article/10.1088/1742-6596/825/1/012012/pdf DOI : 10.1088/1742-6596/825/1/012012 |
|
来源: IOP | |
【 摘 要 】
Displacement of an electrical arc between two parallel arc runners is studied with high-speed imaging, voltage, current and pressure measurements. The experimental set-up is detailed from the current source to the post-treatment methods. The influence of intensity, gas exhausts and volume behind the moving contact on arc commutation and movement are investigated. In the context of Low-Voltage Circuit Breaker (LVCB), it is shown that for high-intensity arcs, evacuating the hot gas is necessary for a good motion of the arc. Furthermore, a configuration of exhaust allowing a quick movement will not work for all current levels.
【 预 览 】
Files | Size | Format | View |
---|---|---|---|
Experimental investigations on arc movement and commutation in the Low-Voltage Circuit Breaker | 1194KB | download |