32nd UIT (Italian Union of Thermo–fluid-dynamics) Heat Transfer Conference | |
RELAP5-3D thermal hydraulic analysis of the target cooling system in the SPES experimental facility | |
物理学;力学 | |
Giardina, M.^1 ; Castiglia, F.^1 ; Buffa, P.^1 ; Palermo, G.^1 ; Prete, G.^2 | |
Department of Energy, Information Engineering and Mathematical Models (DEIM), University of Palermo, Viale delle Scienze-Parco d'Orléans, Palermo | |
90128, Italy^1 | |
National Institute of Nuclear Physics, National Laboratory of Legnaro, Italy^2 | |
关键词: Experimental facilities; Isotope separation on line; RELAP5; Safety analysis; SPES; Thermal hydraulic system code; Thermal-hydraulic analysis; Thermo-fluid dynamics; | |
Others : https://iopscience.iop.org/article/10.1088/1742-6596/547/1/012032/pdf DOI : 10.1088/1742-6596/547/1/012032 |
|
学科分类:力学,机械学 | |
来源: IOP | |
![]() |
【 摘 要 】
The SPES (Selective Production of Exotic Species) experimental facility, under construction at the Italian National Institute of Nuclear Physics (INFN) Laboratories of Legnaro, Italy, is a second generation Isotope Separation On Line (ISOL) plant for advanced nuclear physic studies. The UCx target-ion source system works at temperature of about 2273 K, producing a high level of radiation (105Sv/h), for this reason a careful risk analysis for the target chamber is among the major safety issues. In this paper, the obtained results of thermofluid-dynamics simulations of accidental transients in the SPES target cooling system are reported. The analysis, performed by using the RELAP5-3D 2.4.2 qualified thermal-hydraulic system code, proves good safety performance of this system during different accidental conditions.