会议论文详细信息
32nd UIT (Italian Union of Thermo–fluid-dynamics) Heat Transfer Conference
Borehole modelling: a comparison between a steady-state model and a novel dynamic model in a real ON/OFF GSHP operation
物理学;力学
De Rosa, M.^1 ; Ruiz-Calvo, F.^2 ; Corberán, J.M.^2 ; Montagud, C.^2 ; Tagliafico, L.A.^1
DIME/TEC, Division of Thermal Energy and Environmental Conditioning, University of Genoa, Via All'Opera Pia, Genoa
16145, Italy^1
Instituto de Ingeniería Energética, Universitat Politècnica de València, Camino de Vera sn, Valencia
46022, Spain^2
关键词: Borehole heat exchangers;    Complex energy systems;    Design and optimization;    Heating and cooling;    Operating condition;    Short-term simulation;    Steady-state modeling;    Temperature evolution;   
Others  :  https://iopscience.iop.org/article/10.1088/1742-6596/547/1/012008/pdf
DOI  :  10.1088/1742-6596/547/1/012008
学科分类:力学,机械学
来源: IOP
PDF
【 摘 要 】

The correct design and optimization of complex energy systems requires the ability to reproduce the dynamic thermal behavior of each system component. In ground source heat pump (GSHP) systems, modelling the borehole heat exchangers (BHE) dynamic response is especially relevant in the development of control strategies for energy optimization purposes. Over the last years, several models have been developed but most of them are based on steady- state approaches, which makes them unsuitable for short-term simulation purposes. In fact, in order to accurately predict the evolution of the fluid temperatures due to the ON/OFF cycles of the heat pump, it is essential to correctly characterize the dynamic response of BHE for very short time periods. The aim of the present paper is to compare the performance of an analytical steady-state model, available in TRNSYS environment (Type 557), with a novel short-term dynamic model. The new dynamic model is based on the thermal-network approach coupled with a vertical discretization of the borehole which takes into account both the advection due to the fluid circulating along the U-tube, and the heat transfer in the borehole and in the ground. These two approaches were compared against experimental data collected from a real GSHP system installed at the Universitat Politecnica de Valencia. The analysis was performed comparing the outlet temperature profiles predicted by both models during daily standard ON/OFF operating conditions, both in heating and cooling mode, and the between both approaches were highlighted. Finally, the obtained results have been discussed focusing on the potential impact that the differences found in the prediction of the temperature evolution could have in design and optimization of GSHP systems.

【 预 览 】
附件列表
Files Size Format View
Borehole modelling: a comparison between a steady-state model and a novel dynamic model in a real ON/OFF GSHP operation 1788KB PDF download
  文献评价指标  
  下载次数:18次 浏览次数:16次