2018 International Conference of Green Buildings and Environmental Management | |
The influence of internal heat exchanger on energy efficiency and environmental effects of the Heat Pump using Low-GWP Refrigerants as substitutes | |
土木建筑工程;生态环境科学 | |
Yuqing, Zhao^1 ; Yun, Dai^1 ; Gaoyan^1 ; Lanyi, Xie^1 ; Xiangyang, Hou^1 ; Jianling, Gao^1 | |
School of Civil Engineering, North China University of Technology, No.5, Jinyuanzhuang Road, Shijingshan District, Beijing | |
100144, China^1 | |
关键词: Energy performance; Experimental analysis; Heat pumps; Internal heat exchanger; Mass percentage; R1234ze; | |
Others : https://iopscience.iop.org/article/10.1088/1755-1315/186/3/012084/pdf DOI : 10.1088/1755-1315/186/3/012084 |
|
来源: IOP | |
【 摘 要 】
This paper presents an experimental analysis of the influence of heat exchanger on the performance of a heat pump system using Low-GWP refrigerants as replacements for R22. In this work, we compare the energy performance of a monitored heat pump system using NC01(composed of R32, R1234ze(E), and R134a at a mass percentage of 50%:17%:33%), R32 and R1234ze(E) with and without the presence of an internal heat exchanger. From the experimental results, COP reductions of R1234ze(E), NC01 and R32 was 12%, 4% and 1.9% respectively, although the presence of an IHX can help to lessen these reductions between 2 and 6%. The results indicated lower TEWI amounts as a result of using NC01 as an alternative to R22 with the presence of IHT (internal heat exchanger).
【 预 览 】
Files | Size | Format | View |
---|---|---|---|
The influence of internal heat exchanger on energy efficiency and environmental effects of the Heat Pump using Low-GWP Refrigerants as substitutes | 674KB | download |