| Modification split type air conditioning unit by installing internal heat exchanger and condenser precooling | |
| 地球科学;经济学 | |
| Ambarita, H.^1 | |
| Sustainable Energy and Biomaterial Centre of Excellent, Universitas Sumatera Utara, Kampus USU, Jl. Almamater, Medan | |
| 20155, Indonesia^1 | |
| 关键词: Additional equipment; Air conditioning units; Compressor power; Internal heat exchanger; Positive impacts; | |
| Others : https://iopscience.iop.org/article/10.1088/1755-1315/126/1/012018/pdf DOI : 10.1088/1755-1315/126/1/012018 |
|
| 来源: IOP | |
PDF
|
|
【 摘 要 】
In this paper, a modified of air conditioning (AC) system is proposed. In the modified system, an internal heat exchanger and condenser precooling unit are installed. The objective is to explore the effect of the additional equipment to the performance of the system. An AC with compressor power of 1 PK is modified and compared with the original one. The results show that ER of the modified system is higher than the original one in order of 3.6%. The work of the compressor of the modified system is 12.5% lower than work of the compressor without modification. Finally, the COP of the modified system is 11.71% higher than the original one. These facts reveal that the combination of IHX and condenser precooling shows positive impact on the performance of the AC. It is recommended to use the modified system to improve the energy efficiency of the Air Conditioning system.