Comparative analysis of heat dissipation panels for a hybrid cooling system integrated in buildings
能源学;生态环境科学
Zuazua-Ros, A.^1 ; Ramos, J.C.^2 ; Martin-Gómez, C.^1 ; Gómez-Acebo, Tomás^2 ; Pisano, A.^2
Construction, Building Services and Structures Department, Universidad de Navarra, Pamplona
31180, Spain^1
TECNUN School of Engineering, Universidad de Navarra, San-Sebastián
20018, Spain^2
关键词: Comparative analysis;    Cooling Capacity;    Cooling panels;    Dissipation elements;    Dissipation potential;    Dissipation ratio;    Main parameters;    Thermal Performance;   
Others  :  https://iopscience.iop.org/article/10.1088/1755-1315/154/1/012008/pdf
DOI  :  10.1088/1755-1315/154/1/012008
学科分类:环境科学(综合)
来源: IOP
PDF
【 摘 要 】

The use of cooling panels as heat dissipation elements integrated in buildings has been previously investigated by the authors. Those elements would be connected to the condenser and would dissipate the heat in a passive form. Following the research, this study analyses and compares the thermal performance of two heat dissipation panels as part of a hybrid cooling system. Both panels were experimentally tested under different variables, thus having nine scenarios for each panel. Additionally, an already validated model was applied. The empirical results show a considerable difference between the cooling capacity among them, doubling the daily average ratio in one scenario. The heat dissipation ratios vary between 106 and 227 W/m2in the first case and 140 and 413 W/m2in the second. Regarding the model applicability, the average error for each panel was 4.0% and 8.5%. The bond between the metal sheet and the pipes of the panels has proven to be the main parameter to assure the highest heat dissipation potential of each panel.

【 预 览 】
附件列表
Files Size Format View
Comparative analysis of heat dissipation panels for a hybrid cooling system integrated in buildings 1014KB PDF download
  文献评价指标  
  下载次数:38次 浏览次数:6次