2019 2nd International Conference of Green Buildings and Environmental Management | |
Research on new water-cooled textile air conditioning system | |
生态环境科学 | |
Liu, Boyu^1 ; Ma, Jingkai^2 ; Chen, Wu^1 | |
National Engineering Laboratory for Advanced Yarn and Fabric Formation and Clean Production, Wuhan Textile University, 430200, China^1 | |
National Engineering Laboratory for Advanced Yarn and Fabric Formation and Clean Roduction, Wuhan Textile University, 430200, China^2 | |
关键词: Air exchanges; Air-conditioning design; Electric energies; Process requirements; Spring temperatures; Temperature and humidities; Temperature and relative humidity; | |
Others : https://iopscience.iop.org/article/10.1088/1755-1315/310/3/032022/pdf DOI : 10.1088/1755-1315/310/3/032022 |
|
学科分类:环境科学(综合) | |
来源: IOP | |
![]() |
【 摘 要 】
Aiming at the existing textile air conditioning system in China, the temperature and relative humidity do not meet the process requirements, the air exchange is uneven, and the energy consumption is high.This paper refers to the working principle of traditional textile air conditioner, combined with the requirements of temperature and humidity in textile workshop, and designs a new water-cooled textile air conditioning system from three aspects: air conditioning design, various components and Flow simulation.The results show that the temperature and relative humidity errors are 4.3% and 2.0%, respectively. The spring temperature can be maintained at 22.1 °C, the relative humidity is 77.3%, the electric energy is saved by 30%, and the water is savedby 27%.
【 预 览 】
Files | Size | Format | View |
---|---|---|---|
Research on new water-cooled textile air conditioning system | 699KB | ![]() |