【 摘 要 】
Tracer gas dilution decay method is a convenient tool for measurement of actual air exchange in building. The article presents the results of measurements of natural air exchange in the selected, airtight rooms. A two-point and multi-point method were used to collect data and calculate the results. The standard procedure for the selection of the optimal measurement time was also included. In tight spaces with low air exchange, the measurement results depend on the assumed duration of measurements. It was found that the duration of measurements of several hours and the multipoint method allow to obtain convergent results.