Analysis and treatment of the shutdown reasons of ultra-supercritical 1000MW steam turbine generator set | |
生态环境科学 | |
Li, Wanjun^1 ; Li, Xiaoxia^2 ; Huang, Tianqi^1 ; Niu, Qingliang^1 | |
Huadian Electric Power Research Institute Co. LTD., Jinan | |
250014, China^1 | |
CRRC Wind Power (ShanDong) CO. Ltd, Jinan | |
250022, China^2 | |
关键词: Effective measures; Fault analysis; Fault treatment; Feed pumps; Leakage problems; Maintenance records; On-site inspection; Steam turbine-generator set; | |
Others : https://iopscience.iop.org/article/10.1088/1755-1315/300/4/042013/pdf DOI : 10.1088/1755-1315/300/4/042013 |
|
学科分类:环境科学(综合) | |
来源: IOP | |
【 摘 要 】
When a power plant ultra-supercritical 1000MW steam turbine generator set is running normally, the electric valve at the outlet of A steam feed pump appears serious leakage. Through on-site inspection and inspection of maintenance records, starting from the structure of the electric valve, the leakage fault of the electric valve at the outlet of A steam feed pump is diagnosed and investigated, and the cause of the fault is accurately analyzed. The leakage problem of the electric valve at the outlet of A steam feed pump has been thoroughly solved by taking effective measures such as changing the packing type, arrangement and improving the installation process.