会议论文详细信息
International science and technology conference "Earth science"
A Calculation of Volume of Explosion Hazard Zone and Explosion Pressure in Oil Storage Tanks
Kopylov, P.^1 ; Nazarov, V.P.^2 ; Fedotkin, D.V.^1
All Russian Research Institute for Fire Protection of EMERCOM of Russia, Balashikha, Moscow Region, Russia^1
State Fire Academy of EMERCOM of Russia, Moscow, Russia^2
关键词: Air mixtures;    Explosion hazards;    Explosion pressure;    Hazardous area;    Oil storage tank;    Saturated vapor;    Type II;    Upper flammability limits;   
Others  :  https://iopscience.iop.org/article/10.1088/1755-1315/272/2/022033/pdf
DOI  :  10.1088/1755-1315/272/2/022033
来源: IOP
PDF
【 摘 要 】
It is shown that for determination of tanks stability to explosion of gas-air mixtures it is important to calculate explosion pressure in dynamics (at filling or emptying of the tank) depending on level of filling. A method for determination of explosion pressure in the tanks is proposed, taking into account the dependency of the volume of hazardous area from time. It is shown that the formation of the zone of explosive concentrations is divided into three types depending on the ratio of saturated vapor concentration to the lower and upper flammability limits, and for RVS-5000 tanks the type II is characteristic. The results of calculations of explosion pressure from the time of evaporation taking into account the volume of explosion-hazardous area for a tank of 5000 m3 are presented.
【 预 览 】
附件列表
Files Size Format View
A Calculation of Volume of Explosion Hazard Zone and Explosion Pressure in Oil Storage Tanks 507KB PDF download
  文献评价指标  
  下载次数:20次 浏览次数:18次