会议论文详细信息
4th International Conference on Advances in Energy Resources and Environment Engineering
A Novel Sensor to Measure the DC Bias in Distribution Power Transformers
能源学;生态环境科学
Xiong, Xiaoman^1 ; Li, Chunmei^1 ; Yang, Yuxuan^1 ; Liu, Xiaoyu^1
Sichuan Electric Power Corporation Power Economic Research Institute, Chengdu Sichuan
610041, China^1
关键词: DC bias;    Dc current;    DC voltage;    Ground return;    HVDC systems;    Long distance transmission;    Point of common coupling;    Secondary-side;   
Others  :  https://iopscience.iop.org/article/10.1088/1755-1315/237/6/062046/pdf
DOI  :  10.1088/1755-1315/237/6/062046
学科分类:环境科学(综合)
来源: IOP
PDF
【 摘 要 】
With the advantages of long-distance transmission and correlation of the power system, HVDC project has become increasingly popular of implementation in china. When the HVDC system operated in mono-pole ground return mode, the DC bias occurred by the accumulated DC current at the point of common coupling of transformers and cause series bad influences to transformer itself. In order to reduce the DC bias phenomena in the secondary side of the transformer, it is of prime need to accurate and fast sense the DC bias. Firstly, this paper narrative the effect of DC bias to transformers. Then, a novel DC bias sensor is raised, which achieve the objective by measuring the DC voltage that across the resistance caused by the following of DC current. Last, simulations are taken to assess the accuracy and validity of the proposed DC bias sensor, and simulation results prove that the proposed sensor can accurately and quickly sense the DC bias.
【 预 览 】
附件列表
Files Size Format View
A Novel Sensor to Measure the DC Bias in Distribution Power Transformers 397KB PDF download
  文献评价指标  
  下载次数:12次 浏览次数:28次