会议论文详细信息
12th International Civil Engineering Post Graduate Conference;3rd International Symposium on Expertise of Engineering Design
Vibration criteria analysis on floor at laboratory room
土木建筑工程
Chik, T.N.T.^1 ; Yew, T.A.^1 ; Ibrahim, M.H.W.^1 ; Yusoff, N.A.^2
Jamilus Research Centre, Faculty of Civil and Environmental Engineering, Universiti Tun Hussein Onn Malaysia, Johor, Batu Pahat
86400, Malaysia^1
RECESS Centre, Faculty of Civil and Environmental Engineering, Universiti Tun Hussein Onn Malaysia, Johor, Batu Pahat
86400, Malaysia^2
关键词: Finite element modelling;    Floor vibrations;    Laboratory buildings;    Root Mean Square;    Sensitive equipment;    Vibration criteria;    Vibration excitation sources;    Vibration problem;   
Others  :  https://iopscience.iop.org/article/10.1088/1755-1315/220/1/012021/pdf
DOI  :  10.1088/1755-1315/220/1/012021
学科分类:土木及结构工程学
来源: IOP
PDF
【 摘 要 】

Engineer is now facing a significant challenge related to the vibration problem in the structure. Building is subjected to the significant dynamic load induced by people will generate the dynamic forces. The objectives of this study are to model a three storey building by using Finite Element Modelling (FEM) and perform the vibration criteria plot on floor at laboratory building due to people walking. A vibration excitation source is generated by people walking at four different points. The Finite Element (FE) analyses such as modal analysis and transient analysis are carried out in ANSYS and the data are further generated via MATLAB (VSATs) software to assess the vibration criteria plot (VC). After evaluation, the vibration criterion of survey laboratory fell under VC-E which contributed to the highest percentage plot which is 40 percent of vibration criterion at the certain points. The maximum Root Mean Square (RMS) curve for survey laboratory is 10 micrometers/sec which fell under VC-C at the certain points. VC-C criterion is the good standard for most lithography and inspection equipment up to 1 micron detail size. Thus, survey laboratory has fulfilled the vibration requirements based on the Gordon standard since the VC-E (less severe) criterion is more suitable to allocate the survey equipment for the certain location. The floor vibration performance is analyzed and compared with the guideline and standard such as Generic Vibration Criteria by Gordon in which the vibration level is under minimum permissible level for sensitive equipment.

【 预 览 】
附件列表
Files Size Format View
Vibration criteria analysis on floor at laboratory room 850KB PDF download
  文献评价指标  