Remaining life assessment 150/20 kV trafo with isolation degradation method
工业技术(总论);机械制造
Warman, E.^1 ; Rahmat, M.^1 ; Fahmi, F.^1
Department of Electrical Engineering, University of Sumatera Utara, Jl. Almamater Kampus USU, Medan
20155, Indonesia^1
关键词: Environmental temperature;    Hotspot temperature;    Load factors;    Main station;    Remaining life assessments;    Top oil;    Working temperatures;   
Others  :  https://iopscience.iop.org/article/10.1088/1757-899X/505/1/012054/pdf
DOI  :  10.1088/1757-899X/505/1/012054
学科分类:工业工程学
来源: IOP
PDF
【 摘 要 】

The life of a transformator (trafo) is determined by some of the conditions experienced by the trafo when the trafo is loaded. One of the conditions that provide high effect the life of the trafo is the amount of working temperature on the trafo. The high lowerature trafo at load time is determined by the amount of load generated, the ability of the trafo to release the heat generated and the circumstances surrounding the trafo. In this research, the determination of trafo life by using isolation degradation method by measuring the temperature of top-oil, hot-spot temperature, and the amount of load generated by the trafo. The study was conducted by taking a case study of 150KV/20KV trafo on Titi Kuning Substation. From the results of research on the trafo type, trafostar obtained the rest of the life of the trafo 2 in the Main Station Titi Kuning can survive for 11 years. With a load factor of 0.72 pu, a total hot-spot temperature of 169.20C, and an environmental temperature of 260C.

【 预 览 】
附件列表
Files Size Format View
Remaining life assessment 150/20 kV trafo with isolation degradation method 720KB PDF download
  文献评价指标  
  下载次数:5次 浏览次数:34次