会议论文详细信息
2nd International Conference on Frontiers of Materials Synthesis and Processing
Analysis and Treatment of the Cause of Heating of Single-core XLPE Cable GIS Terminal
Zhang, Hao^1 ; Hu, Xiaoli^1 ; Duan, Yubing^1 ; Su, Jianjun^1 ; Yao, Jinxia^1 ; Gu, Chao^1 ; Liu, Hui^1
State Grid Shandong Electric Power Research Institute, Jinan, China^1
关键词: High frequency HF;    Infrared temperature measurements;    Infrared thermal imager;    Partial discharge detection;    Partial discharge monitoring systems;    Sheath currents;    XLPE cables;   
Others  :  https://iopscience.iop.org/article/10.1088/1757-899X/493/1/012039/pdf
DOI  :  10.1088/1757-899X/493/1/012039
来源: IOP
PDF
【 摘 要 】

In this paper, the heat generation of 110kV cable GIS terminal discovered by infrared thermal imager is briefly described. The causes of heat generation are discussed by means of sheath current detection and circulation calculation, and further analysed by high frequency partial discharge monitoring system, timely handling of equipment hidden dangers, to avoid the occurrence of vicious accidents. Through the analysis and judgment of this accident, the significance of infrared temperature measurement, sheath current detection technology and high frequency partial discharge detection technology for the discovery of cable defects is proved, which provides a basis and reference for future work.

【 预 览 】
附件列表
Files Size Format View
Analysis and Treatment of the Cause of Heating of Single-core XLPE Cable GIS Terminal 795KB PDF download
  文献评价指标  
  下载次数:7次 浏览次数:12次