学位论文详细信息
North Carolina Performance Enhanced Relocatable Classroom Project:An Evaluation of Design Changes to a Typical Relocatable Classroom
Energy 10;efficient construction;daylighting;building modeling;energy efficient;school trailer;modular classroom
Raper, Garrett Matthew ; Dr. Herbert M. Eckerlin, Committee Co-Chair,Dr. James W. Leach, Committee Chair,Raper, Garrett Matthew ; Dr. Herbert M. Eckerlin ; Committee Co-Chair ; Dr. James W. Leach ; Committee Chair
University:North Carolina State University
关键词: Energy 10;    efficient construction;    daylighting;    building modeling;    energy efficient;    school trailer;    modular classroom;   
Others  :  https://repository.lib.ncsu.edu/bitstream/handle/1840.16/712/etd.pdf?sequence=1&isAllowed=y
美国|英语
来源: null
PDF
【 摘 要 】

In this study, the energy consumption of two relocatable classrooms located on the southern portion of the campus of Chapel Hill High School in Chapel Hill, NC is investigated.One classroom, the control, was specified and purchased by the Chapel Hill-Carrboro City School System.The other is a performance enhanced classroom designed by the Florida Solar Energy Center and purchased by the North Carolina Solar Center.Both classrooms are 24' by 40' modular structures, completely underpinned, and located adjacent to one another for a side by side comparison.The energy consumption and indoor conditions of each classroom are monitored by a data-logging system that also records outdoor conditions via a weather station.The performance enhanced classroom is equipped with a 3 ton, SEER 12 heat pump controlled by a Bard CS2000 unit, six skylights, increased insulation and envelope sealing, a demand control ventilation system with an energy recovery wheel, and a day lighting system controlled by occupancy sensors.The control classroom is equipped with a wall-mounted 10 kW electric furnace/air conditioning system.A programmable thermostat was also installed in the control classroom after two months of data was collected.A building model is prepared using the Energy-10 software package to estimate the impact the various design changes have on the energy consumption of each classroom.

【 预 览 】
附件列表
Files Size Format View
North Carolina Performance Enhanced Relocatable Classroom Project:An Evaluation of Design Changes to a Typical Relocatable Classroom 696KB PDF download
  文献评价指标  
  下载次数:11次 浏览次数:17次