科技报告详细信息
Investigation of Room Ventilation for Improved Operation of a Downdraft Table.
Jayaraman, B. ; Kristoffersen, A. ; Finlayson, E. ; Gadgil, A.
Technical Information Center Oak Ridge Tennessee
关键词: Computational fluid dynamics;    Indoor air pollution;    Air pollution control;    Room ventilation;    Configuration;   
RP-ID  :  DE2004835163
学科分类:工程和技术(综合)
美国|英语
来源: National Technical Reports Library
PDF
【 摘 要 】

We report a computational fluid dynamics (CFD) study on containment of airborne hazardous materials in a ventilated room containing a downdraft table. Specifically, we investigate the containment of hazardous airborne material obtainable under a range of ventilation configurations. The desirable ventilation configuration should ensure excellent containment of the hazardous material released from the workspace above the downdraft table. However, increased airflow raises operation costs, so the airflow should be as low as feasible without compromising containment. The airflow is modeled using Reynolds Averaged Navier Stokes equations with a high Reynolds number k-epsilon turbulence model. CFD predictions are examined for several ventilation configurations. Based on this study, we find that substantial improvements in containment are possible concurrent with a significant reduction in airflow, compared to the existing design of ventilation configuration.

【 预 览 】
附件列表
Files Size Format View
DE2004835163.pdf 543KB PDF download
  文献评价指标  
  下载次数:8次 浏览次数:14次