科技报告详细信息
Use of Air2Air Technology to Recover Fresh-Water from the Normal Evaporative Cooling Loss at Coal-Based Thermoelectric Power Plants
Mortensen, Ken
Spx Cooling Technologies Incorporated
关键词: Evaporative Cooling;    Combustion;    Exhaust Gases;    Materials Recovery;    Cooling Towers;   
DOI  :  10.2172/981920
RP-ID  :  None
RP-ID  :  FC26-06NT42725
RP-ID  :  981920
美国|英语
来源: UNT Digital Library
PDF
【 摘 要 】

This program was undertaken to build and operate the first Air2Air{trademark} Water Conservation Cooling Tower at a power plant, giving a validated basis and capability for water conservation by this method. Air2Air{trademark} water conservation technology recovers a portion of the traditional cooling tower evaporate. The Condensing Module provides an air-to-air heat exchanger above the wet fill media, extracting the heat from the hot saturated moist air leaving in the cooling tower and condensing water. The rate of evaporate water recovery is typically 10%-25% annually, depending on the cooling tower location (climate).

【 预 览 】
附件列表
Files Size Format View
981920.pdf 3790KB PDF download
  文献评价指标  