| Use of Air2Air Technology to Recover Fresh-Water from the Normal Evaporative Cooling Loss at Coal-Based Thermoelectric Power Plants | |
| Mortensen, Ken | |
| Spx Cooling Technologies Incorporated | |
| 关键词: Evaporative Cooling; Combustion; Exhaust Gases; Materials Recovery; Cooling Towers; | |
| DOI : 10.2172/981920 RP-ID : None RP-ID : FC26-06NT42725 RP-ID : 981920 |
|
| 美国|英语 | |
| 来源: UNT Digital Library | |
PDF
|
|
【 摘 要 】
This program was undertaken to build and operate the first Air2Air{trademark} Water Conservation Cooling Tower at a power plant, giving a validated basis and capability for water conservation by this method. Air2Air{trademark} water conservation technology recovers a portion of the traditional cooling tower evaporate. The Condensing Module provides an air-to-air heat exchanger above the wet fill media, extracting the heat from the hot saturated moist air leaving in the cooling tower and condensing water. The rate of evaporate water recovery is typically 10%-25% annually, depending on the cooling tower location (climate).
【 预 览 】
| Files | Size | Format | View |
|---|---|---|---|
| 981920.pdf | 3790KB |
PDF