科技报告详细信息
Measuring OutdoorAir Intake Rates Using Electronic Velocity Sensors at Louvers and Downstream of Airflow Straighteners
Fisk, William ; Sullivan, Douglas ; Cohen, Sebastian ; Han, Hwataik
Lawrence Berkeley National Laboratory
关键词: Calibration;    Heating;    Flow Rate;    Hvac Systems;    Commercial Building, Control, Hvac, Measurement, Outdoor Air, Ventilation;   
DOI  :  10.2172/944427
RP-ID  :  LBNL-1250E
RP-ID  :  DE-AC02-05CH11231
RP-ID  :  944427
美国|英语
来源: UNT Digital Library
PDF
【 摘 要 】

Practical and accurate technologies are needed for continuously measuring and controlling outdoor air (OA) intake rates in commercial building heating, ventilating, and air conditioning (HVAC) systems. This project evaluated two new measurement approaches. Laboratory experiments determined that OA flow rates were measurable with errors generally less than 10percent using electronic air velocity probes installed between OA intake louver blades or at the outlet face of louvers. High accuracy was maintained with OA flow rates as low as 15percent of the maximum for the louvers. Thus, with this measurement approach HVAC systems do not need separate OA intakes for minimum OA supply. System calibration parameters are required for each unique combination of louver type and velocity sensor location but calibrations are not necessary for each system installation. The research also determined that the accuracy of measuring OA flow rates with velocity probes located in the duct downstream of the intake louver was not improved by installing honeycomb airflow straighteners upstream of the probes. Errors varied with type of upstream louver, were as high as 100percent, and were often greater than 25percent. In conclusion, use of electronic air velocity probes between the blades of OA intake louvers or at the outlet face of louvers is a highly promising means of accurately measuring rates of OA flow into HVAC systems. The use of electronic velocity probes downstream of airflow straighteners is less promising, at least with the relatively small OA HVAC inlet systems employed in this research.

【 预 览 】
附件列表
Files Size Format View
944427.pdf 267KB PDF download
  文献评价指标  
  下载次数:10次 浏览次数:20次