科技报告详细信息
Sensor for Individual Burner Control of Firing Rate, Fuel-Air Ratio, and Coal Fineness Correlation
Hill, Wayne ; Demler, Roger ; Mudry, Robert G.
Foster-Miller
关键词: Calibration;    Fuel-Air Ratio;    Testing;    Burners;    01 Coal, Lignite, And Peat;   
DOI  :  10.2172/886734
RP-ID  :  none
RP-ID  :  FC26-03NT41846
RP-ID  :  886734
美国|英语
来源: UNT Digital Library
PDF
【 摘 要 】

To minimize program cost, additional testing was performed in concert with EPRI-funded testing at the Coal Flow Test Facility in late July. The major focus of this effort was noise reduction. As it turned out, the main source of the noise proved to be related to electrical grounding issues and the adjustments needed to address these problems took most of the test period. Once those changes were in place, a very limited quantity of high quality data was obtained and an excellent correlation between the dynamic signature and coal flow was obtained. Additional data were then collected during August. Unfortunately, the sensor signal for the August data collection proved to be extremely weak. Therefore, Airflow Sciences will collect additional laboratory data in October before proceeding with the collection of field data. This will allow the calibration to be expanded to include a wider range of flow conditions and improve the potential applicability to data to be collected at the coal plants.

【 预 览 】
附件列表
Files Size Format View
886734.pdf 242KB PDF download
  文献评价指标  
  下载次数:7次 浏览次数:18次