科技报告详细信息
Measuring rates of outdoor airflow into HVAC systems | |
Fisk, William J. ; Faulkner, David ; Sullivan, Douglas P. ; Delp, Woody | |
Lawrence Berkeley National Laboratory | |
关键词: 32 Energy Conservation, Consumption, And Utilization; Air; Flow Rate; Hvac Systems; | |
DOI : 10.2172/824629 RP-ID : LBNL--51583 RP-ID : AC03-76SF00098 RP-ID : 824629 |
|
美国|英语 | |
来源: UNT Digital Library | |
【 摘 要 】
During the last few years, new technologies have been introduced for measuring the flow rates of outside air into HVAC systems. This document describes one particular technology for measuring these airflows, a system and a related protocol developed to evaluate this and similar measurement technologies under conditions without wind, and the results of our evaluations. We conclude that the measurement technology evaluated can provide a reasonably accurate measurement of OA flow rate over a broad range of flow, without significantly increasing airflow resistance.
【 预 览 】
Files | Size | Format | View |
---|---|---|---|
824629.pdf | 365KB | download |