Measuring rates of outdoor airflow into HVAC systems
Fisk, William J. ; Faulkner, David ; Sullivan, Douglas P. ; Delp, Woody
Lawrence Berkeley National Laboratory
关键词: 32 Energy Conservation, Consumption, And Utilization;    Air;    Flow Rate;    Hvac Systems;   
DOI  :  10.2172/824629
RP-ID  :  LBNL--51583
RP-ID  :  AC03-76SF00098
RP-ID  :  824629
美国|英语
来源: UNT Digital Library
PDF
【 摘 要 】

During the last few years, new technologies have been introduced for measuring the flow rates of outside air into HVAC systems. This document describes one particular technology for measuring these airflows, a system and a related protocol developed to evaluate this and similar measurement technologies under conditions without wind, and the results of our evaluations. We conclude that the measurement technology evaluated can provide a reasonably accurate measurement of OA flow rate over a broad range of flow, without significantly increasing airflow resistance.