Technical Basis for the Use of Alarming Personal Criticality Detectors to Augment Permanent Nuclear Incident Monitor (NIM) Systems in Areas Not Normally Occupied
Yates, K.R.
Savannah River Site (S.C.)
关键词: Radiation Monitors;    Criticality;    Recommendations;    Personnel Dosimetry;    61 Radiation Protection And Dosimetry;   
DOI  :  10.2172/811370
RP-ID  :  N-TRT-G-00001
RP-ID  :  AC09-96SR18500
RP-ID  :  811370
美国|英语
来源: UNT Digital Library
PDF
【 摘 要 】

The technical basis for the use of alarming personal criticality detectors (APCDs) to augment permanent Nuclear Incident Monitor (NIM) Systems in areas not normally occupied is evaluated. All applicable DOE O 420.1A and ANSI/ANS-8.3-1997 criticality alarm system requirements and recommendations are evaluated for applicability to APCDs. Based on this evaluation, design criteria and administrative requirements are presented for APCDs. Siemens EPD/Mk-2 and EPD-N devices are shown to meet the design criteria. A definition of not normally occupied is also presented.